<<BACK

YRA3        DIN RAIL MOUNT   
8RA3       8 PIN PLUG-IN
11RA3        11 PIN PLUG-IN

Mode of operation:

Function  [A3], The timer needs to be permanently supplied. It the command contact (S2) is closed for a time in excess of the set time, the relay will energise at the set time. If contact S2 should be opened and closed during timing, the timer will store each 'closed' time period until the sum of 'closed' time periods reaches the set time, when the relay will energise. this will occur however long the interval between closed times, provided that the timer is not reset. To reset, the supply must be removed for 50mS.

Features:

LED  operation indicator.
Two versions (S,L) each with four time ranges.
Selection of time range by switches.
10 Ampere rated single pole change-over contacts.
Only 24mm wide case.
Delay on energise.

Voltages:

230Vac
110Vac
48Vac/dc
24Vac/dc
12Vdc

Timing Ranges:

There are two versions, each have four selectable time ranges.

S L
0,06 - 0.6s 15 - 150s
0.25 - 2.5s 1 - 10m
2 - 20s 8 - 80m
16 - 160s 64 - 640m

 

Specification:

Supply tolerance. 0.85 to 1.15 Un
Frequency 50 - 60Hz
Power consumption 7VA at 220Vac     0.6W at 24Vdc
Output. Single pole change-over
Contact material AgNi
Maximum loading 10Aac or 1Adc
Maximum switching voltage 250Vac or 250Vdc
Relay Maximum power rating 2200VA or 30W
Maximum peak current 15A
Mechanical life of relay. 30x106 operations
Electrical life of relay. 2x105 operations at  10A 220Vac resistive load.
Repeat accuracy at a constant ambient. ± 0.5%
Repeat accuracy within 
temperature specification of VDE0435
± 3%
Reset time: After timing.
                 
   
During timing
25mS
50mS
Operating and storage temperature. -20 to +60oC
Connection Screw terminal or plug in
Weight. 80g

Ordering Information:

Type example. YRA3 L 110

Connections: